Let Unified Theory Inc. of Camarillo, CA help you with your next Industrial Process, Mechanical, Structural or Electrical project.
Our team of engineers can handle almost any industrial process system design.
Whether your project is for conveyor controls, emission controls, exhaust systems, air handling systems, fluid systems, materials handling systems or high speed manufacturing, UTI can handle it all.

Engineering Consultants in Southern California

WELCOME TO THE UNIFIED THEORY, INC. (UTI) BLOG


We serve Industrial Clients with Engineering and Architectural Resources, Processing and Facility Needs.




Save Time
Save Money
Access Industry Experts



UTI offers a full range of industrial and commercial architectural services, including project management, construction management and training.

Control Engineering - Breaking News

Friday, January 2, 2009

Thermocouple Data Logger


Omega Engineering are now selling a Thermocouple data logger that plugs directly into a USB port.

The OM-EL-USB-TC data logger measures and stores over 32,000 temperature readings from either a Type J, Type K or Type T thermocouple which plugs into a miniature female thermocouple receptacle at the base of the unit. The user can easily set up the initial data logging parameters including thermocouple type, logging rate, start-time, high/low alarm settings, logging mode and desired temperature units (°C or °F) and also download the stored data by plugging the module straight into a PC’s USB port and running the easy-to-use Windows software.

Downloaded data can then be graphed, printed and exported to other applications such as Excel. The data logger is supplied complete with a long-life lithium battery. Data logger status is indicated by flashing red, green and orange LEDs.

Specifications
Temperature Measurement Range:
Type J: -130 to 900°C (-202 to 1652°F)
Type K: -200 to 1300°C (-328 to 2372°F)
Type T: -200 to 350°C (-328 to 662°F)
Resolution: 0.5°C (1°F)
Accuracy: ±1.0°C (±2.0°F)
Thermocouple Connection: Female subminiature thermocouple connector
Temperature Units: °C or °F selectable in software
Memory: 32,000 readings
Logging Interval: 1 sec, 10 sec, 1 min, 5 min, 30 min, 1 hr, 6 hr, 12 hr
(selectable in software)
High/Low Alarms: Selectable in software
Start Date/Time: Selectable in software
Operating Temperature Range: -10 to 40°C (-14 to 104°F)
Visual Indicators (LEDs): 2 LEDs; the first LED flashes orange to indicate a problem
condition with the data logger such as low battery; the second LED indicates alarm status
and flashes green (temperature within limits) or red (temperature out of limits)
Software: Windows® 2000/XP/VISTA
Power: 1/2 AA 3.6 V lithium battery (included)
Battery Life: 6 months (at 25°C and 1 minute logging interval)
Weight: 43 g (1.5 oz)

Automation.com Featured Products